MTL5582B MTL Intrinsically Safe Isolator 5500 Series RTD-RTD Iso
MTL5582B MTL Intrinsically Safe Isolator 5500 Series RTD-RTD Isolator
MTL 5500 Intrinsically Safe Isolators Resistance Isolator MTL5582B
MTL4582B - MTL5582B RESISTANCE ISOLATOR to repeat RTD signals
The MTLx582B connects to a 2-, 3-, or 4-wire resistance temperature device (RTD) or other resistance located in a hazardous area, isolates it and repeats the resistance to a monitoring system in the safe area. The module is intended typically (but not exclusively) for use with Pt100 3-wire RTDs. Switches enable selection of 2-, 3-, or 4-wire RTD connection. The MTLx582B should be considered as an alternative, non-configurable MTLx575, for use in RTD applications where a resistance input is preferred or needed instead of 4/20mA. The design is notable for its ease of use and repeatability. The number of wires which can be connected on the safe-area side of the unit is independent of the number of wires which can be connected on the hazardous-area side. The module drives upscale in the case of open circuit detection.
Email: anna@cwlyautomation.com
Tel: +86 13667121125 whatsapp/ vk/ telegram also available
Company: CW Green Tech
MTL5582B product specification
SPECIFICATION
See also common specification
Number of channels
One
Location of RTD
Zone 0, IIC, T4 hazardous area
Div. 1, Group A, hazardous location
Resistance source
2-, 3-, or 4-wire* RTDs to BS 1904/DIN 43760 (100Ω at 0°C)
*user selectable by switches (factory set for 3-wire)
Resistance range
10Ω to 400Ω
RTD excitation current